StihlHead460 t1_ixp84s1 wrote
Reply to comment by CloneClem in Lighting Install Question by hahvaggevabba
And OP clearly stated that the mfg provided an equipment ground.
StihlHead460 t1_ixp82pn wrote
Reply to comment by CloneClem in Lighting Install Question by hahvaggevabba
Wrong. See NEC 250.4(A)(4) and 110.3(B)
StihlHead460 t1_ixkuvef wrote
Reply to comment by CloneClem in Lighting Install Question by hahvaggevabba
This is not necessarily accurate advice
StihlHead460 t1_ixp8eg8 wrote
Reply to Lighting Install Question by hahvaggevabba
OP, your choices are pretty much, install as is, knowing that you don't have an equipment ground and it is a less than ideal situation, refeed the sconces with a wiring method that includes an equipment ground, or just run an equipment ground with you existing wiring (same amount of work as option #2)